Cummins 300kw Marine Diesel Generator Set 50HZ,3P,4W,400/230V. 1500r.p.m
MODEL | CCFJ300 | |
Prime Power (50Hz) | 300KW | 375 KVA |
Standby Power (50Hz) | 330KW | 412 KVA |
Voltage(V) | Hz | Phase |
P.F
(cosC) |
Prime Amps (A) |
Prime Ratings
(KW/KVA) |
||
415 | 240 | 50 | 3 | 0.8 | 522 | 300 | 375 |
400 | 230 | 50 | 3 | 0.8 | 541 | 300 | 375 |
380 | 220 | 50 | 3 | 0.8 | 570 | 300 | 375 |
Prime Power (PRP): Prime power is available for an unlimited number of annual hours in variable load application, in accordance with GB/T2820-97 (eqv ISO8528) ; A 10% overload capability is available for a period of 1 hour within a 12-hour period of operation.
Standby Power Rating (ESP): The standby power rating is applicable for supplying emergency power for the duration of a utility power interruption. No overload, utility parallel or negotiated outage operation capability is available at this rating.
● GB/T13032-1991, ISO9001:2008 and CE Quality Control System.
● As to Classification Society, PRIME POWER supply CCS as standard; ABS,BV,BKI,NK or LR is optional.
Manufacturer / Model: Cummins K19-DM,4-cycle,Water Cooled.
Air Intake System: Turbo, Water/Air cooling
Cylinder Arrangement: 6 cylinders in line
Displacement: 19L
Bore and Stroke: 159*159(mm)
Fuel Consumption at 100% Load : 213 g/kw.h
Rated RPM: 1500rpm
Max. Standby Power:358KW/480HP
Governor Type: Electronic Speed Control System
Emission Standard:IMO TIER II, EIAPP Certificate
Alternator Model HCM534C
Power Capacity 400kVa
Efficiency 95.8%
Type Brushless, Self-excited and AVR
Power factor 0.8
Insulation Grade H
Protection Grade IP23(IP44 is optional)
We chat